An arc flash is the light and heat produced as part of an arc fault (sometimes referred to as an electrical flashover), a type of electricity explosion or discharge that results from a connection through air to ground or another voltage phase in an electrical system.
Arc flash is distinctly different from the arc blast, which is the supersonic shockwave produced when the uncontrolled arc vaporizes the metal conductors. Both are part of the same arc fault, and are often referred to as simply an arc flash, but from a safety standpoint they are often treated separately. For example, personal protective equipment (PPE) can be used to effectively shield a worker from the radiation of an arc flash, but that same PPE may likely be ineffective against the flying objects, molten metal, and violent concussion that the arc blast can produce. (For example, category-4 arc-flash protection, similar to a bomb suit, is unlikely to protect a person from the concussion of a very large blast, although it may prevent the worker from being vaporized by the intense light of the flash.) For this reason, other safety precautions are usually taken in addition to wearing PPE, helping to prevent injury. Safe Work Practices for the Electrician by Ray A. Jones, Jane G. Jones -- Jones and Bartlett Publishing 2009 Page 40 However, the phenomenon of the arc blast is sometimes used to extinguish the electric arc by some types of self-blast–chamber circuit breakers.
Arc flash temperatures can reach or exceed at the arc terminals.KM Kowalski-Trakofler, EA Barrett, CW Urban, GT Homce. " Arc Flash Awareness: Information and Discussion Topics for Electrical Workers ". DHHS (NIOSH) Publication No. 2007-116D. Accessed January 10, 2013. The massive energy released in the fault rapidly vaporizes the metal conductors involved, blasting molten metal and expanding plasma outward with extraordinary force. A typical arc flash incident can be inconsequential but could conceivably easily produce a more severe explosion (see calculation below). The result of the violent event can cause destruction of equipment involved, fire, and injury not only to an electrical worker but also to bystanders. During the arc flash, electrical energy vaporizes the metal, which changes from solid state to gas vapor, expanding it with explosive force. For example, when copper vaporizes it suddenly expands by a factor of 67,000 in volume. Electrical Safety in the Workplace By Ray A. Jones, Jane G. Jones -- National Fire Protection Agency 2000 Page 32
In addition to the explosive blast, called the arc blast of such a fault, destruction also arises from the intense radiant heat produced by the arc. The metal plasma arc produces tremendous amounts of light energy from far infrared to ultraviolet. Surfaces of nearby objects, including people, absorb this energy and are instantly heated to vaporizing temperatures. The effects of this can be seen on adjacent walls and equipment - they are often ablated and eroded from the radiant effects.
High-voltage powerlines often operate in the range of tens to hundreds of kilovolts, which can result in very long arc-flashes, often referred to as a flashover. Care must usually be taken to ensure that the lines are insulated with a proper "flashover rating" and sufficiently spaced from each other to prevent an arc flash from spontaneously developing. If the high-voltage lines become too close, either to each other or ground, a corona discharge may form between the conductors. This is typically a blue or reddish light caused by ionization of the air, accompanied by a hissing or frying sound. The corona discharge can easily lead to an arc flash, by creating a conductive pathway between the lines. This ionization can be enhanced during electrical storms, causing spontaneous arc-flashes and leading to power outages.''Electric power generation: Transmission and distribution By S. N. Singh -- PHI Limited 2008 Page 235--236, 260--261
As an example of the energy released in an arc flash incident, in a single phase-to-phase fault on a 480 V system with 20,000 amps of fault current, the resulting power is 9.6 Watt. If the fault lasts for 10 cycles at 60 Hz, the resulting energy would be 1.6 joule. For comparison, Trinitrotoluene releases 2175 J/g or more when detonated (a conventional value of 4,184 J/g is used for TNT equivalent). Thus, this fault energy is equivalent to 380 grams (approximately 0.8 pounds) of TNT. The character of an arc flash blast is quite different from a chemical explosion (more heat and light, less mechanical shock), but the resulting devastation is comparable. The rapidly expanding superheated vapor produced by the arc can cause serious injury or damage, and the intense UV, Visible spectrum, and Infrared light produced by the arc can temporarily and sometimes even permanently blind or cause eye damage to people.
There are four different arc flash type events to be assessed when designing safety programs:
Circuit breakers are often the primary defense against current runaway, especially if there are no secondary fuses, so if an arc flash develops in a breaker there may be nothing to stop a flash from going out of control. Once an arc flash begins in a breaker, it can quickly migrate from a single circuit to the of the panel itself, allowing very high energies to flow. Precautions must usually be used when switching circuit breakers, such as standing off to the side while switching to keep the body out of the way, wearing protective clothing, or turning off equipment, circuits and panels downline prior to switching. Very large switchgear is often able to handle very high energies and, thus, many places require the use of full protective equipment before switching one on. ARC Flash Hazard Analysis and Mitigation by J. C. Das -- IEEE Press 2012
In addition to the heat, light and concussive forces, an arc flash also produces a cloud of plasma and ionized particles. When inhaled, this ionized gas can cause severe burns to the airways and lungs. The charged plasma may also be attracted to metallic objects worn by people in the vicinity, such as earrings, belt buckles, keys, body jewelry, or the frames of glasses, causing severe localized burns. When switching circuits, a technician should take care to remove any metals from their body, hold their breath, and close their eyes. An arc flash is more likely to form in a switch that is closed slowly, by allowing time for an arc to form between the contacts, so it is usually more desirable to "throw" switches with a fast motion, quickly and firmly making good contact. High-current switches often have a system of springs and levers or even pneumatic assists to assist with this.
The effectiveness of protective equipment is measured by its arc rating. The arc rating is the maximum incident energy resistance demonstrated by a material prior to breakopen (a hole in the material) or necessary to pass through and cause a 50% probability of second degree burns. Arc rating is normally expressed in calorie/cm2 (or small calories of heat energy per square centimeter). The tests for determining arc rating are defined in ASTM F1506 Standard Performance Specification for Flame Resistant Textile Materials for Wearing Apparel for Use by Electrical Workers Exposed to Momentary Electric Arc and Related Thermal Hazards.
The selection of appropriate PPE, given a certain task to be performed, is normally handled in one of two possible ways. The first method is to consult a hazard category classification table, like that found in NFPA 70E. Table 130.7(C)(15)(a) lists a number of typical electrical tasks by various voltage levels and recommends the category of PPE that should be worn. For example, when working on 600 V switchgear and performing a removal of bolted covers to expose bare, energized parts, the table recommends a Category 3 Protective Clothing System. This Category 3 system corresponds to an ensemble of PPE that together offers protection up to . The minimum rating of PPE necessary for any category is the maximum available energy for that category. For example, a Category 3 arc-flash hazard requires PPE rated for no less than .
The second method of selecting PPE is to perform an arc flash hazard calculation to determine the available incident arc energy. IEEE 1584 provides a guide to perform these calculations given that the maximum fault current, duration of faults, and other general equipment information is known. Once the incident energy is calculated the appropriate ensemble of PPE that offers protection greater than the energy available can be selected.
PPE provides protection after an arc flash incident has occurred and should be viewed as the last line of protection. Reducing the frequency and severity of incidents should be the first option and this can be achieved through a complete arc flash hazard assessment and through the application of technology such as high-resistance grounding which has been proven to reduce the frequency and severity of incidents.
Arcing time can significantly be reduced by protection based on detection of arc-flash light. Optical detection is often combined with overcurrent information. Light and current based protection can be set up with dedicated arc-flash protective relays, or by using normal equipped with an add-on arc-flash option.
One of the most efficient means to reduce arcing time is to use an active arc flash mitigation device, e.g., an ultra-fast earthing switch (UFES). This type of arc flash mitigation device operates rapidly within a few milliseconds, creating a three-phase short-circuit to ground, which safely redirects fault currents away from the location of the arc flash. Upon activation by an external relay, a fast-moving contact pin makes physical contact with the energized bus, creating the short circuit. By redirecting the fault current, this action provides robust protection for personnel in close proximity to the arc flash and limits damage to equipment by reducing the exposure time to the high-energy event. After operation, the single-use contact pin needs to be replaced, while the main unit remains intact.
Another way to mitigate arc flash is to use a triggered current limiter or commutating current limiter which inserts a low rated continuous current current limiting fuse that melts and interrupts the arc flash within 4 ms. The advantage of this device is that it eliminates the arc flash at the source and does not divert it to another section of the system. A triggered current limiter will always be "Current Limiting" which means it will interrupt the circuit before the first peak current occurs. These devices are electronically controlled and sensed and provide feedback to the user about their operational status. They can also be turned ON and OFF as desired. These devices must be replaced after an operation.
Examples
Precautions
Switching
Live testing
Protecting personnel
Arc flash protection equipment
Reducing hazard by design
Fault current
Arcing time
Distance